Deck Footing Size and Post Height Tables

6 min · Updated 2026-09-28

Use IRC Table R507.3.1 to check deck footing size by soil and supported area, then compare post height, depth and spacing with worked examples.

Written by DueRivaLast reviewed: 2026-09-28Review standard

Use the deck footing calculator to work out the area one post carries from your joist length and post spacing, then read both tables at once. For the full deck footprint and a scope every contractor can price, continue with the deck planning guide.

A deck’s posts stand on footings, and the residential code sizes both with tables: a footing by the deck area its post carries and the soil under it (Table R507.3.1), and a wood post’s greatest height by its size, its species and that same area (Table R507.4). The code calls that area the tributary area: the deck surface a post and its footing hold up. The tables below are the code’s rows for a live load of 40 psf (pounds per square foot), the model code’s minimum for a deck, which Austin keeps; Austin’s ground snow load is 5 psf, so those rows govern there. Los Angeles designs decks for California’s 60 psf, which the last section below covers. The posts are No. 2 grade or better, with the wet service factor built in: the strength reduction for wood that stays damp outdoors. The post heights also assume a 10 psf dead load, the weight of the deck itself, with no snow at the same time as the live load (Table R507.4).

How big should a deck footing be?

Read down to the deck area the post carries, in the table for the soil under the footing. Each row gives a square footing’s side or, for a round footing, its diameter, and in either case the thickness of plain (unreinforced) concrete. A post carrying 60 square feet of deck on clay, at 1,500 psf, needs a square footing 17 inches on a side or a round one 19 inches across, 6 inches thick; on sand, at 2,000 psf, it needs 15 inches square or 17 inches round, still 6 inches thick. The code allows reading between two rows, but not past the 5 to 160 square feet the table covers. The footing is wide enough for the post to bear on it completely, and where a brick or concrete block (CMU) pier stands on it, the footing projects at least 2 inches past the pier on every side.

Minimum deck footing size at a 40 psf live load, on soil bearing 1,500 psf (IRC Table R507.3.1)
Deck area carriedSquare footing, sideRound footing, diameterConcrete thickness
5 sq ft7 in8 in6 in
20 sq ft10 in12 in6 in
40 sq ft14 in16 in6 in
60 sq ft17 in19 in6 in
80 sq ft20 in22 in7 in
100 sq ft22 in25 in8 in
120 sq ft24 in27 in9 in
140 sq ft26 in29 in10 in
160 sq ft28 in31 in11 in
Minimum deck footing size at a 40 psf live load, on soil bearing 2,000 psf (IRC Table R507.3.1)
Deck area carriedSquare footing, sideRound footing, diameterConcrete thickness
5 sq ft7 in8 in6 in
20 sq ft9 in9 in6 in
40 sq ft12 in14 in6 in
60 sq ft15 in17 in6 in
80 sq ft17 in19 in6 in
100 sq ft19 in21 in6 in
120 sq ft21 in23 in7 in
140 sq ft22 in25 in8 in
160 sq ft24 in27 in9 in
Minimum deck footing size at a 40 psf live load, on soil bearing 3,000 psf or more (IRC Table R507.3.1)
Deck area carriedSquare footing, sideRound footing, diameterConcrete thickness
5 sq ft7 in8 in6 in
20 sq ft7 in8 in6 in
40 sq ft10 in12 in6 in
60 sq ft12 in14 in6 in
80 sq ft14 in16 in6 in
100 sq ft15 in17 in6 in
120 sq ft17 in19 in6 in
140 sq ft18 in21 in6 in
160 sq ft20 in22 in7 in

Which soil column to read

Unless a complete geotechnical evaluation says otherwise, the code has you assume the load-bearing values below (Section R401.4.1). Clay and silt are taken at 1,500 psf, the lowest value the footing table has. Where soil data show that expansive, compressible, shifting or otherwise questionable soil is likely, the building official decides whether to require a soil test, and where the building official finds soil bearing less than 1,500 psf likely, a soils investigation sets the value. Ask the city which value it accepts for your lot before reading a firmer soil’s column.

Presumptive load-bearing values of soil and rock (IRC Table R401.4.1(1))
MaterialBearing value
Crystalline bedrock12,000 psf
Sedimentary and foliated rock4,000 psf
Sandy gravel or gravel (GW, GP)3,000 psf
Sand, silty or clayey sand, silty or clayey gravel (SW, SP, SM, SC, GM, GC)2,000 psf
Clay, sandy or silty clay, clayey silt, silt, sandy silt clay (CL, ML, MH, CH)1,500 psf

How deep do deck footings need to be?

A deck footing goes at least 12 inches below undisturbed ground (R507.3.2). Where the deck is attached to a house whose own foundation is protected from frost, the deck’s footings are protected too: below the frost line in the city’s Table R301.2, on solid rock, or by another approved method (R507.3.3). Austin puts its frost line at 12 inches and Los Angeles at 12. A free-standing deck whose joists rest on the ground their whole length, or a small, low one whose joists sit on precast concrete pier blocks, can need no footings at all; the deck joist and beam span guide gives the conditions.

How tall can a deck post be?

Table R507.4 gives the greatest height of a wood post under a single-level deck, measured from the underside of the beam to the top of the footing or pier. Read across from the deck area the post carries to its size. A Southern pine 4×4 carrying 60 square feet may stand up to 11 feet, and a 4×6 up to 13 feet 11 inches; 14 feet is the most these rows allow any post. NP, not permitted, means the code allows no post of that size and species at that area. The code allows reading between two areas, but not past the 20 to 160 square feet the table covers. A notched post, one cut to seat the beam, is sized for the beam as Section R507.5.2 requires.

Maximum deck post height at a 40 psf live load, by deck area carried (IRC Table R507.4): Southern pine
Deck area carried4×44×66×68×8
20 sq ft14′14′14′14′
40 sq ft13′8″14′14′14′
60 sq ft11′13′11″14′14′
80 sq ft9′5″12′14′14′
100 sq ft8′4″10′8″14′14′
120 sq ft7′5″9′8″14′14′
140 sq ft6′9″8′10″14′14′
160 sq ft6′2″8′2″14′14′
Maximum deck post height at a 40 psf live load, by deck area carried (IRC Table R507.4): Douglas fir-larch, hem-fir or spruce-pine-fir
Deck area carried4×44×66×68×8
20 sq ft14′14′14′14′
40 sq ft13′6″14′14′14′
60 sq ft10′10″13′10″14′14′
80 sq ft9′3″11′10″14′14′
100 sq ft8′10′6″14′14′
120 sq ft7′9′5″14′14′
140 sq ft6′2″8′7″14′14′
160 sq ft5′3″7′10″14′14′
Maximum deck post height at a 40 psf live load, by deck area carried (IRC Table R507.4): Redwood, western cedars, ponderosa pine or red pine
Deck area carried4×44×66×68×8
20 sq ft14′14′14′14′
40 sq ft13′2″14′14′14′
60 sq ft10′3″13′6″14′14′
80 sq ft8′1″11′4″14′14′
100 sq ft5′8″9′9″14′14′
120 sq ftNP8′4″14′14′
140 sq ftNP6′9″13′7″14′
160 sq ftNP4′7″9′7″14′

Where a post bears on a concrete footing, it is held against sideways movement by an approved connector or by being embedded at least 12 inches in the surrounding soil or a concrete pier. Where the soil is expansive, compressible, shifting or otherwise questionable, the soil does not count toward that restraint (R507.4.1).

How far apart should deck footings be?

Along a beam, the footings sit under the posts, so they can be no farther apart than the beam’s allowed span, which the span tables give by species, beam size and the joists’ span and cantilever. Between two beams, or a beam and the house, the distance is the joists’ span. Spacing posts farther apart gives each one more deck to carry, and in the tables a larger area can mean a larger footing and a lower maximum post height: for 4×4 and 4×6 posts, and for 6×6 posts in the redwood group above 120 square feet.

Los Angeles

California’s code sets a deck’s live load at 60 psf, and the tables above are the 40 psf rows. The code’s footing table also has 60 psf rows, labeled for a live or ground snow load, but its post table’s 60 psf rows are labeled for a ground snow load, and it has no 60 psf live load row. Los Angeles’s code also narrows a permission for isolated plain concrete footings under columns or pedestals. California’s code permits them in detached one- and two-family dwellings of three stories or less with stud bearing walls; Los Angeles’s permits them there only in seismic design categories A, B or C, the code’s earthquake design classes, and its design criteria table (R301.2(1)) puts the city in D2/E. Neither code says whether this reaches a deck’s footings. Before sizing a Los Angeles deck’s posts or footings from a table, ask the city what it accepts; its code also allows an engineered design, under the Los Angeles Building Code, for any building or structure the residential code covers.

Whether the deck needs a permit at all is a separate question: the deck permit brief gives Austin’s and Los Angeles’s lines, and the deck calculator counts the joists and decking.

Primary sources

What this page was checked against

  • 2024 International Residential Code, Sections R507.3.1 and R507.4: Deck footing size and deck posts

    International Code Council · checked 2026-09-28

    Used for: Minimum deck footing size by tributary area and allowable soil-bearing pressure per Table R401.4.1(1) (R507.3.1): at a 40 psf live or ground snow load, the side of a square footing, the diameter of a round footing and the plain concrete thickness for 5 to 160 sq ft at 1,500, 2,000 and 3,000 or more psf; interpolation permitted, extrapolation not; based on dead plus live or dead plus snow; footing dimensions allowing complete bearing of the post; a 2 in minimum projection on all sides under a brick or CMU pier; tributary area the deck surface supported by post and footings (Table R507.3.1 and notes). Wood post size for single-level decks (R507.4): maximum deck post height at a 40 psf live load by species, 4x4 to 8x8, for 20 to 160 sq ft, measured from the underside of the beam to the top of the footing or pier, 10 psf dead load, No. 2 grade with the wet service factor included, notched posts sized for the beam under R507.5.2, interpolation permitted and extrapolation not, NP not permitted; its 50, 60 and 70 psf rows are for ground snow load (Table R507.4 and notes). Lateral restraint of a post on a concrete footing by approved connectors or at least 12 in of embedment in surrounding soils or concrete piers, surrounding soils not relied on where expansive, compressible, shifting or other questionable soils are present (R507.4.1).

  • 2024 International Residential Code, Section R401.4: Soil tests and presumptive load-bearing values

    International Code Council · checked 2026-09-28

    Used for: Where data indicate expansive, compressible, shifting or other questionable soils are likely, the building official determines whether to require a soil test (R401.4); in lieu of a complete geotechnical evaluation, the values of Table R401.4.1(1) are assumed (R401.4.1): crystalline bedrock 12,000 psf; sedimentary and foliated rock 4,000; sandy gravel or gravel (GW, GP) 3,000; sand, silty sand, clayey sand, silty gravel and clayey gravel (SW, SP, SM, SC, GM, GC) 2,000; clay, sandy clay, silty clay, clayey silt, silt and sandy silt clay (CL, ML, MH, CH) 1,500, with a soils investigation where the building official finds soils under 1,500 psf likely.

  • 2024 International Residential Code, Section R507.3: Deck footings

    International Code Council · checked 2026-09-28

    Used for: Deck footings at least 12 in below undisturbed ground (R507.3.2); where a deck is attached to a frost-protected structure, footings below the frost line of Table R301.2, on solid rock or by other approved methods (R507.3.3); none for a free-standing deck with joists on grade over their entire length, or with joists bearing directly on precast pier blocks at grade without beams or posts, 200 sq ft or less and 20 in or less above grade within 36 in of its edge (R507.3, Exceptions 1 and 2).

  • 2024 International Residential Code, Sections R507.1 to R507.9: Deck materials, footings, posts, beams, joists, decking and attachment

    International Code Council · checked 2026-09-28

    Used for: Decks designed for the live load of R301.5 or the ground snow load of Table R301.2, whichever is greater (R507.1); sawn lumber for posts No. 2 or better (R507.2.1).

  • 2024 International Residential Code, Table R301.5: Minimum uniformly distributed live loads

    International Code Council · checked 2026-09-28

    Used for: Balconies (exterior) and decks: 40 psf.

  • 2025 California Residential Code, Section R507: Exterior decks

    California Building Standards Commission · checked 2026-09-28

    Used for: R507.1 and R507.2.1 read as in the 2024 IRC.

  • 2025 California Residential Code, Tables R507.3.1, R507.4 and R401.4.1(1), and Section R403.1.3.6

    California Building Standards Commission · checked 2026-09-28

    Used for: The same deck footing sizes, labeled for a live or ground snow load, the same deck post heights, whose 60 psf rows are for ground snow load, the same R507.3.2, R507.3.3 and R507.4.1 text, and the same presumptive soil values as the 2024 IRC; isolated plain concrete footings supporting columns or pedestals permitted in detached one- and two-family dwellings three stories or less with stud bearing walls (R403.1.3.6, chapter 4).

  • 2025 California Residential Code, Table R301.5: Minimum uniformly distributed live loads

    California Building Standards Commission · checked 2026-09-28

    Used for: Balconies (exterior) and decks: 60 psf, a California amendment to the model code's 40 psf.

  • Austin City Code, §§ 25-12-241 and 25-12-243: International Residential Code and local amendments

    City of Austin · checked 2026-09-28

    Used for: Adopts the 2024 IRC (§ 25-12-241); its deletions and local amendments leave Chapter 4, Section R507 and Table R301.5 unchanged, and its Table R301.2 sets a ground snow load of 5 psf and a frost line depth of 12 in (§ 25-12-243).

  • Los Angeles Municipal Code, Chapter IX, Article 1.5: Los Angeles Residential Code

    City of Los Angeles · checked 2026-09-27

    Used for: Adopts the California Residential Code by reference, except its Chapter 1 and Appendix AS (Sec. 91.5.100).

  • Los Angeles Municipal Code, Sec. 91.5.400: Foundations

    City of Los Angeles · checked 2026-09-28

    Used for: Adopts Chapter 4 of the California Residential Code with amendments; isolated plain concrete footings supporting columns or pedestals permitted in detached one- and two-family dwellings located in Seismic Design Category A, B or C that are three stories or less with stud bearing walls (91.5.403.1.3.6); no amendment to Section R401.4.

  • Los Angeles Municipal Code, Sec. 91.5.500: Floors

    City of Los Angeles · checked 2026-09-28

    Used for: Adopts Chapter 5 of the California Residential Code with one amendment, for openings in horizontal diaphragms (91.5.503.2.4); none to Section R507.

  • Los Angeles Municipal Code, Sec. 91.5.300, Table R301.2(1): Climatic and geographic design criteria

    City of Los Angeles · checked 2026-09-28

    Used for: Table R301.2(1): ground snow load 0, seismic design category D2/E, frost line depth 12 in; the city's amendments to Chapter 3 leave Table R301.5 unchanged, and engineered design under the Los Angeles Building Code is permitted for all buildings and structures (Secs. 91.5.300, 91.5.301.1.3).